HVAC and Generators
Emergency power generation equipment - Generators
A volcanic ashfall can cause
electricity outages and issues with power supply. Therefore, use of emergency power generation equipment (Generator
Sets or GenSets) may be necessary. Air intakes on generators are
vulnerable to airborne
ash
and need to be protected.
Heating, Ventilation and Air-Conditioning (HVAC)
Air intakes on heating, ventilation and air-conditioning (HVAC)
systems are vulnerable to volcanic
ash
ingestion.
Ash
Ingress through air intake and condenser units: ash ingress may
cause ash accumulation in the radiator and air filters, reducing air
flow and and HVAC condenser system performance. Reduced airflows may
cause stalling and overheating.
-
High humidity significantly increases
ash
adhesion and thus blockage
-
Filters are generally not designed to cope with the suspended
particle volumes seen in volcanic
ash
falls, so require regular inspection and replacement
- HVAC systems with low fan speeds block more readily
-
Horizontal air-intakes and condensers ingest significantly less
ash
than vertical systems
General Instructions for HVAC and Generators
How to prepare
At-risk facilities should develop operational plans for managing
ash
fall events, including a priority schedule and standardised
procedures for inspecting, maintaining and cleaning.
Physical mitigation options:
-
Install hoods over air intake to reduce direct
ash
ingestion (see bottom left figure)
-
Add temporary filtration to external air intakes, monitor and
replace as needed
-
Seal or cover sensitive equipment, such as external fuel valves
and switches
Cleaning Guidance:
-
Vacuum or gently (30 psi or less) blow away excess
ash
from air intakes or condensers, then wipe down with a cloth. Air
filters should be removed before cleaning
-
Wet methods for
ash
cleanup are not recommended, as they may promote clogging of
radiator fins, or cause short-circuits
How to respond
-
Initiate priority schedule for inspection, cleaning and
preventative maintenance
-
Regularly check and service air and fuel intakes and filters
(stock spares
-
Frequency of air filter replacement could be as high as every 30
minutes during high rates of
ash
fall. In this case, step up preventative maintenance
-
Maintain a clean site, especially in front of air intakes, to
reduce remobilisation of
ash
- Use dry methods where possible
-
Store collected
ash
in bags to prevent remobilisation " Ensure stockpiled ash is
well clear of equipment and air intakes
-
Beware wet
ash
maybe conductive. Isolate and earth energised apparatus as
appropriate
-
Advise customers/users not to clean electrical equipment and to
limit the use of water in clean up, and to be careful when
cleaning near electrical equipment